LCD Operation:
LCD control panel consists of LCD display board, LED and buttons, which displays
and controls these information including Utility, Inverter, Bypass, Load, Frequency,
Fault, Running, alarm information, function setting information.
ADVANCE PROTECTION FOR:
Small & medium datacenter
IT, Networking, Storage and Telecom
Infrastructure, Industrial and Medical
FEATURE
Rack/Tower Convertible Design
Patented Mimic LCD Display May be Rotated by Simply Pushing Front Button
True Online Double Conversion with DSP Control
High Output Power Factor at PF.0.9
Charger/Fan Status on the LCD Display
Green Concept Design with Superior Input
Voltage Window for Energy Saving
Hot-Swappable Battery
3-level intelligent Charging Method
Support Generator Input
Efficiency up to 90%
Estimated Remaining Time displayed on the LCD.
Support Economic(ECO) Operation Mode
Cold Start
Power Shedding May Turn Off Uncritical Load in Battery Backup
Emergency Power Off (EPO)
Frequency Converter Mode Is Settable
Input | Model Capacity (VA/W) Nominal voltage Operating voltage range Operating frequency range Power factor Max. input current(A) |
ZC-GP 3KVA 3KVA /2400W 220/230Vac 165-275Vac 50/60Hz (+5%) >0.97 (with filter) 24 |
Output | Output voltage Output frequency Crest factor Efficiency Harmonic distortion (THD) |
220Vac(+0.5%) /230Vac(+0.5%) 50/60Hz( + 0.5%) 3:1 (max) >82% <1.5%(linear load) |
Battery | Battery voltage | 192Vdc |
SYSTEM FEATURES | Transfer time Overload Communication interface |
Oms (Line mode - Battery mode) >125%: 1min, >150%: 200ms RS232, SNMP(optional), Dry contact (optional) |
ENVIRONMENTAL | Operating temperature Storage temperature Humidity range Altitude Noise leve |
0-40°C 25-55°C 0-95% (non-condensing) <1500m <55dB |
PHYSICAL | Dimension WxDxH (mm) Net weight (S/H) (kg) |
305 x 585 x 864 99/54 |
STANDARDS | Safety EMC |
IEC/EN62040-1; IEC/EN60950-1 IEC/EN62040-2;IEC61000-4-2;1EC61000-4-3;EC61000-4-4 IEC61000-4-5;IEC61000-EMC 4-6:IEC61000-4-8 |